Chapter 7

Program the Redundant Controller

Use this table to determine the Retain Test Edits on Switchover setting that suits

your application.

To change the Retain Test Edits on Switchover setting, click the Redundancy tab

in the Controller Properties then click Advanced.

Figure 56 - Retain Test Edits on Switchover

If you need to

Then

Prevent a test edit from faulting both the primary and secondary

controller

Leave Retain Test Edits on Switchover

unchecked

Keep test edits active, even in the event of a switchover and at the risk

of faulting both controllers

Check Retain Test Edits on Switchover