Install the Enhanced Redundancy System

Chapter 3

3. Wait for the redundancy module to complete its start-up scroll messages.

Check Module and status indicators. Wait 45 seconds before you begin

updating the 1756-RM firmware. During this time, the redundancy

module conducts internal operations to prepare for an update.

4. Launch ControlFLASH software and click Next to begin the update

process.

Logix5563

Redundancy Module

Redundancy Module

CH2 CH1 OK

Alphanumeric Display

OK indicator is red during self-

test, and turns green if

firmware is already

downloaded.

Power Supply

indicator is green.

TIP

If it is a new module, wait until APPLICATION UPDATE
REQUIRED is displayed. The status indicator flashes red.