App e - redundancy object attributes, Redundancy object attributes, Appendix e – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 273: Appendix

Advertising
background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

273

Appendix

E

Redundancy Object Attributes

Use this table of redundancy object attributes as a reference when programming

to obtain the status of your redundancy system.

For this information

Get this attribute

Data

Type

GSV/SSV

Description

Redundancy status of the entire

chassis.

ChassisRedundancyState

INT

GSV

If

Then

16#2

Primary with synchronized secondary

16#3

Primary with disqualified secondary

16#4

Primary with no secondary

16#10

Primary locked for update

Redundancy state of the partner

chassis.

PartnerChassis

RedundancyState

INT

GSV

If

Then

16#8

Synchronized secondary

16#9

Disqualified secondary with primary

16#E

No partner

16#12

Secondary locked for update

Redundancy status of the controller.

ModuleRedundancy State

INT

GSV

If

Then

16#2

Primary with synchronized secondary

16#3

Primary with disqualified secondary

16#4

Primary with no secondary

16#6

Primary with synchronizing secondary

16#F

Primary locking for update.

16#10

Primary locked for update

Redundancy state of the partner.

PartnerModule

RedundancyState

INT

GSV

If

Then

16#7

Synchronizing secondary

16#8

Synchronized secondary

16#9

Disqualified secondary with primary

16#E

No partner

16#11

Secondary locking for update

16#12

Secondary locked for update

Results of the compatibility checks

with the partner controller.

CompatibilityResults

INT

GSV

If

Then

0

Undetermined

1

No compatible partner

2

Fully compatible partner

Advertising