Chapter 8

Monitor and Maintain an Enhanced Redundancy System

Verify System Qualification

After you have completed programming your redundant system and have

downloaded your program to the primary controller, check the system status to

verify that the system is qualified and synchronized.

Check Qualification Status via Module Status Displays

You can view qualification status by using the status displays and indicators of the

secondary redundancy module and the primary and secondary ControlNet and

EtherNet/IP communication modules.

TIP

The system qualification process can take several minutes. After a
qualification command or a switchover, allow time for qualification to
complete before taking action based on the qualification status.

Table 35 - Synchronized System

Primary Chassis Display

Secondary Chassis Display

Redundancy Module

Communication Module Redundancy Module

Communication Module

PRIM

PwQS

SYNC

QS

Table 36 - Qualifying System

Primary Chassis Display

Secondary Chassis Display

Redundancy Module

Communication Module Redundancy Module

Communication Module

PRIM and QFNG

PQgS

QFNG

QgS

Table 37 - System with a Primary and Disqualified Secondary

Primary Chassis Display

Secondary Chassis Display

Redundancy Module

Communication Module Redundancy Module

Communication Module

PRIM

PwDS

DISQ

Either:

CMPT (modules are

compatible)

DSNP (no partner is

present)