Determine use of ip address swapping, Use ip address swapping – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 78

Advertising
background image

78

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Chapter 4

Configure the EtherNet/IP Network

Determine Use of IP Address Swapping

Depending on your EtherNet/IP network configuration, you can choose to use

IP address swapping between your partnered EtherNet/IP communication

modules in the event of a switchover.

If you are using different subnets, you are responsible for programming your

system to use the address and subnet of the new primary chassis in the event of a

switchover.

Use IP Address Swapping

If you use IP address swapping, assign the same values for these configuration

parameters on both EtherNet/IP communication modules in the partnered set:

IP address
Subnet mask
Gateway address

This graphic shows a partnered set of EtherNet/IP communication modules

during initial configuration.

Figure 17 - EtherNet/IP Communication Modules’ IP Addresses During System Configuration

If your partnered EtherNet/IP communication modules are on

the

Then

Same subnet

use IP address swapping

Different subnets

do not use IP address swapping

CH2 CH1 OK

CH2 CH1 OK

Primary chassis

Secondary Chassis

Assigned IP Address: 192.168.1.3

Advertising