244

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Appendix C

Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

Upgrade Ethernet Modules

When Rotary Switches Are Set

between 2…254

This section includes the procedure to upgrade your Ethernet communication

modules when the modules rotary switches are set to 2…254 and you are unable

to interrupt the primary.

Before starting the following steps, complete

steps 1…5 on page 250

.

If your system is controlling a process and using rotary switches, follow these

steps.

1. Set the mode switch of the primary and secondary controllers to REM.

If the redundant controllers in both chassis of the redundant chassis pair

are not in Remote Program (REM) mode, the redundancy firmware

upgrade cannot be completed.

2. Open RSLinx Classic software and browse to the redundancy module.
3. Right-click the redundancy module and choose Module Configuration.

4. Click the Configuration tab.

IMPORTANT

This procedure must be executed before steps 6…12 of

Upgrade by Using Redundancy

System Update on page 250

.

IMPORTANT

This is a change from prior releases’ upgrade procedures.

IMPORTANT

Please note, you must be physically present at the location where the redundant
chassis are located to do this upgrade.

IMPORTANT

You can only upgrade from firmware revision 19.052 or later to firmware revision
20.054. These steps apply when upgrading from firmware revision 19.052 or later to
firmware revision 20.054.