Assign lowest node numbers to remote controlnet – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 39

Advertising
background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

39

Design an Enhanced Redundancy System

Chapter 2

Assign Lowest Node Numbers to Remote ControlNet Modules

Do not assign the lowest ControlNet node addresses to ControlNet modules in

the redundant chassis pair.

If you assign the lowest ControlNet node addresses to ControlNet modules in

the redundant chassis pair, you can experience these system behaviors:

Upon a switchover, you can lose communication with I/O modules,

produced tags, and consumed tags.

Removing a ControlNet module from the redundant chassis can result in

lost communication with I/O modules, produced tags, and consumed

tags.

If the entire system loses power, you can be required to cycle power to the

primary chassis to restore communication.

Set Partnered ControlNet Module Switches to the Same Address

Where ControlNet modules are used as partners in a redundant chassis pair, you

must set the node address switches to the same node address. The primary

ControlNet modules can be at even or odd node addresses.

For example, if partnered ControlNet modules are assigned to nodes 12 and 13

of the ControlNet network, set the node address switches of the modules to the

same address of 12.

Figure 6 - Example of Switch Address for Partnered ControlNet Modules

CH2 CH1 OK

CH2 CH1 OK

ControlNet Module Switches

Advertising