Program the Redundant Controller

5. On the Synchronization tab, click Disqualify Secondary.

6. In RSLogix 5000 software, access the Controller Properties dialog box and

click the Nonvolatile Memory tab.

7. Click Load/Store.
8. Click <-- Store and then click Yes.

When the store is complete, we go online with the secondary controller.

9. Complete

steps 6

8

to store the project in nonvolatile memory of the

secondary controller.

10. In RSLinx Classic software, open the RMCT for one of the redundancy

modules in the redundant pair.

11. In the Synchronization tab, click Synchronize Secondary.

12. In the Configuration tab, set the Auto-Synchronization option to your

desired setting.