Program the Redundant Controller

Chapter 7

Multiple Periodic Tasks

In a project where multiple periodic tasks are used, the point where program

execution begins after a switchover depends on the following:

Crossload and synchronization settings
Task priority settings

As with the continuous task, the controller begins executing at the program that

follows the last crossload and synchronization point.

In addition, a higher priority task may interrupt a lower priority task. If a

switchover occurs during or just after the higher priority task executes and the

lower priority task has not been completed, then the lower priority task and

programs are executed from the point at which the last crossload occurred.

This diagram demonstrates how tasks at different priorities execute if a

switchover occurs while a lower priority task is executing. Note that the crossload

and synchronization points in this example are set to occur only at the end of the

last program within the tasks and not at each program’s end.

Figure 35 - Normal Periodic Task Execution (no switchover)

ATTENTION: If you use multiple periodic tasks, program all crucial
outputs within the highest-priority task. Failure to program outputs in

the highest-priority task can result in outputs changing state if a
switchover occurs.