258

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Appendix C

Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

8. Complete steps

2

7

for each module in the secondary chassis, including a

new controller, if applicable.

Once you have upgraded the firmware for each module in the secondary chassis,

prepare the RSLogix 5000 project for the upgrade.

Step 9: Prepare the RSLogix 5000 Project for the Upgrade

Complete these steps to prepare the RSLogix 5000 program and controllers for

the upgrade.

1. Launch RSLogix 5000 software and go online with the primary controller.
2. Verify that the watchdog time is set to a value that corresponds with the

requirements of the enhanced redundancy system revision and your

application.

See

Minimum Value for the Watchdog Time

on

page 177

for information

about calculating the minimum watchdog time.

3. Cancel or assemble any pending test edits.
4. Remove all Sequential Function Chart (SFC) forces from the project.
5. Verify that no changes need to be made to the following:

I/O forces
I/O configuration

After this step, changes to I/O cannot be made until after the enhanced

redundancy system revision upgrade is complete and both chassis are

synchronized.

6. If you are upgrading an enhanced redundancy system, revision 16.81 or

earlier, disable CST Mastership.

7. Configure the controllers and communication modules in the redundant

chassis pair as necessary.

8. Save the project.
9. Go offline.

10. Click Controller Properties.

IMPORTANT

Ethernet communication modules that have rotary switches set must have been
previously updated using

Upgrade Ethernet Modules When Rotary Switches Are Set

between 2…254 on page 244

.

Controller Properties