246

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Appendix C

Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

10. Make a note of the primary Ethernet module’s Port Configuration

including the following:
IP Address
Network Mask
Gateway Address

11. Disconnect the Ethernet cable or cables from the secondary Ethernet

module.

12. Remove the secondary Ethernet module from the secondary chassis.

Record the original rotary switch settings, as you need to set them back

later.

Set the rotary switches to 999.

13. Reinsert the secondary Ethernet module into the secondary chassis.
14. Bridging

across the backplane (or via the Ethernet module’s USB port),

configure the secondary Ethernet module’s Port Configuration to match

the primary Ethernet module’s Port Configuration from

step 10

.

15. Update the secondary Ethernet module to firmware revision 5.008 by

following these steps.
a. Launch ControlFLASH software and click Next.