250

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Appendix C

Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

Upgrade by Using Redundancy

System Update

You can upgrade an enhanced redundancy system revision to another while your

process continues to run. This is known as Redundancy System Update (RSU).

Complete these steps to upgrade your redundancy system from one enhanced

redundancy system revision to another enhanced redundancy revision while

your process continues to run.

1.

Step 1: Before You Begin

2.

Step 2: Upgrade the Workstation Software

3.

Step 3: Download and Install the Redundancy Firmware Bundle

4.

Step 4: Upgrade the Redundancy Module Configuration Tool

5.

Step 5: Add the EDS Files

6.

Step 6: Prepare the Redundant Chassis for the Firmware Upgrade

7.

Step 7: Upgrade the Primary Chassis Redundancy Module Firmware

8.

Step 8: Upgrade the Secondary Redundancy Module Firmware and All

Other Modules’ Firmware in the Secondary Chassis

9.

Step 9: Prepare the RSLogix 5000 Project for the Upgrade

10.

Step 10: Lock the System and Initiate a Switchover to Upgrade

11.

Step 11: Upgrade the New Secondary Chassis Firmware

12.

Step 12: Synchronize the Redundant Chassis

IMPORTANT

RSU is available only when upgrading from an enhanced redundancy system revision
to another. You cannot use this process to upgrade from a standard redundancy
system to an enhanced redundancy system.

IMPORTANT

Any Ethernet communication modules that have the rotary switch set must first be
updated using the

Upgrade Ethernet Modules When Rotary Switches Are Set between

2…254 on page 244

IMPORTANT

You can only upgrade from firmware revision 19.052 or later to firmware revision
20.054. These steps apply when upgrading from firmware revision19.052 or later to
firmware revision 20.054.