Ok status indicators, Table 44 - ok status indicator, Communication status indicator – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 232: Table 45 - communication status indicator

Advertising
background image

232

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Appendix A

Status Indicators

OK Status Indicators

The OK status indicator reveals the current redundancy module state.

Communication Status Indicator

The communication status indicator indicates activity on the redundancy

module communication between chassis in the redundant chassis pair.

Table 44 - OK Status Indicator

Indicator State

Description

Off

No power is applied to the redundancy module.
If necessary, apply power.

Solid red

One of these conditions exists:

The redundancy module is conducting a self-test during powerup.

No action necessary.

The redundancy module has experienced a major fault.

Cycle power to clear the fault. If the major fault does not clear, replace the module.

Flashing red

One of these conditions exists:

The redundancy module is updating its firmware.

No action necessary.

The redundancy module has been configured improperly.

Check the module configuration and correct any issues.

The redundancy module has experienced a minor failure.

Cycle power to clear the fault. If the major fault does not clear, replace the module.

Solid green

The redundancy module is operating normally. No action required.

Flashing green

The redundancy module is operating normally but is not communicating with the

other redundancy module.
If necessary, establish communication with the other redundancy module.

Table 45 - Communication Status Indicator

Indicator State

Description

Off

One of these conditions exist:

No power is currently applied to the module.

Apply power to the module.

There is no communication between redundancy modules in the redundant chassis

pair.
Diagnose the redundancy configuration to determine why no communication is

taking place.

Red < 1 second

The module has been started and has established partner communication.
No action required.

Solid red

The module has experienced a critical communication failure.
Cycle power to clear the fault. If the major fault does not clear, replace the module.

Flashing green > 250 ms

Communication activity is present.
No action required.