Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Appendix C

Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

You are now ready to lock the system and initiate a locked switchover to update

the primary chassis. Continue with

Step 10: Lock the System and Initiate a

Switchover to Upgrade

.

Step 10: Lock the System and Initiate a Switchover to Upgrade

Once you have downloaded the RSLogix 5000 project you prepared, complete

these steps to lock your system and initiate a switchover.

1. Open the RMCT for the redundancy module in the primary chassis by

right-clicking on the RM module in RSLinx Classic software and selecting

Module Configuration.

2. Click the System Update tab.

3. Click Lock For Update, then click Yes.
4. Wait for the system to lock.

IMPORTANT

Remain offline while completing these steps.
Once you have locked the system, do not abort the system lock. Aborting the

system lock during this procedure clears the project from the secondary

controller.

Do not disconnect any communication cables while completing these steps.
Completing a locked switchover causes SFC instructions to be reset to their

initial state. This may result in SFC instructions executing twice.