Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

167

Program the Redundant Controller

Chapter 7

Use Periodic Tasks

If you have multiple tasks in your project, changing the System Overhead Time

Slice does not affect how communication is serviced. To increase the time to

service communication when multiple tasks are used, configure the periodic tasks

such that more time might be available to service communication.

If you use periodic tasks, communication is serviced any time a task is not

running. For example, if you configure your task period at 80 ms and the task

executes in 50 ms, the controller has 30 ms out of every 80 ms to service

communication.

Figure 50 - Periodic Task Execution and Service Communication

If you use multiple periodic tasks, verify the following:

The execution time of a highest priority task is significantly smaller than

its period.

The total execution time of all your tasks is significantly less than the

period of the lowest priority tasks.

Verifying those settings generally leaves enough time for service communication.

The example configuration of tasks shown here demonstrates those

configuration settings.

TIP

While you can use multiple periodic tasks in your
redundant controller program, use the fewest number of
tasks possible.

50 ms

50 ms

50 ms

Task Execution

30 ms

30 ms

30 ms

Service Communication

Periodic Task

Periodic Task

Periodic Task