Chapter 9

Troubleshoot a Redundant System

You can also browse to the redundancy module in RSLinx Classic software to

determine if it is connected to the network. A red X over the redundancy module

indicates the module is not in the chassis.

Figure 66 - Missing Redundancy Module in RSLinx Classic Software

To correct the missing module anomaly, first verify that the redundancy module

is correctly installed in the chassis and it is properly powered. Then check the

intermodule cable that connects the redundancy modules.

After you have verified that the module is installed and powered, you may need to

synchronize the chassis by using the synchronization commands in the

Synchronization tab. Use the synchronization commands if your Auto-

Synchronization parameter for the chassis is not set to Always.