Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

Appendix C

Upgrade the System Software

Upgrading your system software requires you to make many considerations and

decisions. Make sure you are fully aware of how your specific application will be

affected when you upgrade system software:

If you are upgrading to enhanced redundancy system, revision 16.081 or

earlier, you are not required to upgrade any software.

If you are upgrading to enhanced redundancy system, revision 19.052 or

later, you must upgrade this software:

RSLogix 5000 software
RSLinx Enterprise communication software or RSLinx Classic

communication software, depending on which RSLinx software you

are using in the application

Due to potential changes to your application when upgrading to enhanced

redundancy system, you may need to install any of the this software:

FactoryTalk Alarms and Events

FactoryTalk Batch

RSNetWorx for ControlNet

RSNetWorx for EtherNet/IP

Upgrade the Controllers

You may need to upgrade your controllers when upgrading to an enhanced

redundancy system. This table describes which controllers are available for

system upgrades.

Controllers Available in Standard

Redundancy Systems

Controllers Available in Enhanced

Redundancy Systems

1756-L61
1756-L62
1756-L63
1756-L64

All revisions

1756-L61
1756-L62
1756L63
1756-L63XT
1756-L64

Revision 19.052 or later only
1756-L65

Revision 19.053 or later only
1756-L72
1756-L73
1756-L74
1756-L75

Revision 20.054 or later only
1756-L71