Monitor and Maintain an Enhanced Redundancy System
Chapter 8
Conduct a Test Switchover
Complete these steps to verify that your redundant system switches over as
expected. Your system must be fully-qualified before you begin.
1. In RSLinx Classic software, access the RMCT for the primary
redundancy module.
2. Click the Synchronization tab.
3. Click Initiate Switchover.
The Redundancy Configuration Tool dialog box opens.
4. Click Yes.
The switchover begins.
5. View your HMI or other status-monitoring device to verify that the
switchover was successful.