Ok status indicators, Table 41 - ok status indicator, Ch1 and ch2 status indicators – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 229: Table 42 - ch1 and ch2 status indicators

Advertising
background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

229

Status Indicators

Appendix A

OK Status Indicators

The OK status indicator reveals the current redundancy module state.

CH1 and CH2 Status Indicators

The CH1 and CH2 status indicators reveal the following module states.

Table 42 - CH1 and CH2 Status Indicators

Table 41 - OK Status Indicator

Indicator State

Description

Off

No power is applied to the redundancy module.
If necessary, apply power.

Solid red

One of these conditions exists:

The redundancy module is conducting a self-test during powerup.

No action necessary.

The redundancy module has experienced a major shutdown fault.

Cycle power to clear the fault. If the major fault does not clear, replace the module.

Flashing red

One of these conditions exists:

The redundancy module is updating its firmware.

No action necessary.

The redundancy module has been configured improperly.

Check the module configuration and correct any issues.

The redundancy module has experienced a major fault that may be cleared

remotely using the RMCT.

Solid green

The redundancy module is operating normally. No action required.

Flashing green

The redundancy module is operating normally but is not communicating with the

other redundancy modules in the same chassis.
If necessary, establish communication with the other redundancy module.

Indicator State

Description

Off

One of these conditions exists:

No power

RM major fault

NVS update

Solid red

One of these conditions exists:

No transceiver plugged in

Faulted or failed transceiver detected

Transceiver with incorrect or vendor ID detected

Intermittent red

For 1 s, then off, indicates powerup.

Flashing red

One of these conditions exists:

Redundant channel error

No cable connection

Intermittent green

(1)

On for 256 ms for each packet received, then off. Active operating channel. (Channel

used for data communication between the partner 1756-RM2/A modules.)

Flashing green

(1)

Indicates that this channel is operating as the back-up channel and is ready to

become the Active channel if the current Active channel fails.

Unknown

Operating state is not yet determined.

Active

Channel is operating normally as the active channel.

Advertising