Design an Enhanced Redundancy System
Chapter 2
You can bridge these networks via a remote chassis:
• ControlNet
• DeviceNet
• EtherNet/IP
• Universal Remote I/O
• Data Highway Plus
This table indicates what system components can be used with each network
connected to a redundant system.
Table 8 - Communication Networks Available For Use with Enhanced Redundancy Systems
Network
Connection to Redundant System
Component
I/O
HMI
ControlNet
Directly to redundant chassis
Yes
Yes
Via a bridge
No
Yes
DeviceNet
Via a bridge
Yes
Yes
EtherNet/IP
Directly to redundant chassis
Yes - Enhanced
Redundancy System,
Revision 19.052 or later
Yes
(1)
(1) To avoid a brief loss of communication with the redundant chassis pair in the event of a switchover, we recommend
that you connect the HMI to the redundant chassis pair via a bridge from an EtherNet/IP network to a ControlNet
network. For more information see
Possible Communication Delays on EtherNet/IP Networks on page 36
.
Via a bridge
No
Yes
Universal Remote I/O
Via a bridge
Yes
Yes
Data Highway Plus
Via a bridge
Yes
Yes