Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

43

Design an Enhanced Redundancy System

Chapter 2

You can bridge these networks via a remote chassis:

ControlNet
DeviceNet
EtherNet/IP
Universal Remote I/O
Data Highway Plus

This table indicates what system components can be used with each network

connected to a redundant system.

Table 8 - Communication Networks Available For Use with Enhanced Redundancy Systems

Network

Connection to Redundant System

Component
I/O

HMI

ControlNet

Directly to redundant chassis

Yes

Yes

Via a bridge

No

Yes

DeviceNet

Via a bridge

Yes

Yes

EtherNet/IP

Directly to redundant chassis

Yes - Enhanced

Redundancy System,

Revision 19.052 or later

Yes

(1)

(1) To avoid a brief loss of communication with the redundant chassis pair in the event of a switchover, we recommend

that you connect the HMI to the redundant chassis pair via a bridge from an EtherNet/IP network to a ControlNet
network. For more information see

Possible Communication Delays on EtherNet/IP Networks on page 36

.

Via a bridge

No

Yes

Universal Remote I/O

Via a bridge

Yes

Yes

Data Highway Plus

Via a bridge

Yes

Yes