Program the Redundant Controller

Program to Minimize Scan

Times

Because your system switchover time is impacted by your total program scan

time, there are several aspects of your program that must be as efficient as possible

to facilitate the fastest possible switchover. The sections that follow indicate

methods of making your program more efficient to minimize your program scan

time.

These methods make your program more efficient and minimize program scan

times:

Use a 1756-L7x Controller with a 1756-RM2/A Redundancy Module

Use Multiple Controllers

Minimize the Number of Programs

Manage Tags for Efficient Crossloads

Use Concise Programming

Use a 1756-L7x Controller with a 1756-RM2/A Redundancy Module

Beginning with enhanced redundancy system revision 19.053, you can use

1756-L7

x controllers in your application. Relative to the redundancy module

being used, the 1756-L7

x controllers scan the controller program faster than

1756-L6

x controllers. The 1756-L7x controllers also scan the controller program

fastest if the enhanced redundancy system uses the 1756-RM2/A redundancy

module.

If your application needs better controller performance, we recommend that you

update from 1756-L6

x controllers to 1756-L7x controllers and use 1756-RM2/

A redundancy modules.

Use Multiple Controllers

When possible, use multiple controllers in your redundant system. If you use

multiple controllers, you can strategically program between the controllers so the

program execution and scan times are faster.

For more information about controllers that can be paired in redundant chassis,

see

Components of an Enhanced Redundancy System on page 24

.

IMPORTANT

Only the 1756-L72, 1756-L73, 1756-L74, and 1756-L75 controllers can be used
in conjunction with the 1756-RM2/A redundancy modules and revision

19.053. See

Components Available for Use in a Redundant Chassis Pair on

page 24

.