Configure the ControlNet Network

Chapter 5

Network Update Time

The network update time (NUT) that you specify for your redundant system

impacts your system performance and your switchover response time. Typical

NUTs used with redundant systems range from 5…10 ms.

NUTs with Multiple ControlNet Networks

You can choose to use multiple ControlNet networks with your enhanced

redundancy system.

Figure 28 - Example of Two ControlNet Networks

When you use multiple ControlNet networks, the networks must use compatible

NUTs. Compatible NUTs are determined based on the network that uses the

smallest NUT.

CH2 CH1 OK

CH2 CH1 OK

ControlNet Network 1
NUT = 5 ms

ControlNet Network 2
NUT =

21 ms