Minimum Value for the Watchdog Time

To set Watchdog time for your 1756-L6

x controllers, use this table to determine

which equation to use to calculate the time for each task.

The

maximum_scan_time is the maximum scan time for the entire task when the

secondary controller is synchronized.

To set the 1756-L7

x initial task tuning, follow these steps.

1. Monitor the Max Scan Time for each task while the redundant chassis pair

is synchronized.

2. Set the Watchdog times for each task to 3 times the Max Scan Time.

3. Use the Logix5000 Task Monitor Tool to configure each Task Period.

(1)

Adjust the Task periods of each so that the maximum scan time is less than

80% of the task period rate.

Adjust the Task periods so that the Logix CPU % utilization is never above

75%.

While performing these tests, the HMI and any other external systems

must be connected to the Logix controller.

Download the Project

Download the project only to the primary controller. When the secondary

controller is synchronized, the system automatically crossloads the project to the

secondary controller.

If

Then use this equation

Using ControlNet I/O ms

(2 * maximum_scan_time) + 150

Using Ethernet I/O ms

(2 * maximum _scan_time) + 100

IMPORTANT

This works only when there is no Continuous task configured in the Logix application.

(1) See the PlantPAx Automation System Reference Manual, publication

PROCES-RM001

.

IMPORTANT

Verify that there are no task overlaps.

IMPORTANT

If the secondary chassis was qualified and becomes disqualified after you
download the project, verify that you have enabled the controller for
redundancy.