Module status display, Table 47 - major fault code messages, Reset the module – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 234: Check the cable

Advertising
background image

234

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Appendix A

Status Indicators

Module Status Display

A character string scrolls across the Module Status Display to indicate the fault

type. The character string displays the fault type in either of these ways:

Two

to four-character word abbreviations

Alpha numeric codes

This table describes the two to four-character word abbreviations.

Table 47 - Major Fault Code Messages

1st Word

2nd Word

3rd Word

4th Word

Error Description

CFG

LOG

ERR

Configuration log error. No action is required.

COMM

RSRC

ERR

Communication resource error. Reset the redundancy

module.

COMM

RSRC

ERR

PRT1

Port1 Communication resource error on Backplane.

Reset the redundancy module and check the chassis.

COMM

RSRC

ERR

PRT2

Port2 Communication resource error on redundancy

link. Complete these tasks:

1. Reset the module.

2. Check the cable.

COMM

ERR

PRT1

Port1 Communication error, Backplane communication.

Check or replace the chassis.

COMM

ERR

PRT2

Port2 Communication error on the redundancy link.

Check or replace the single-mode cable.

COMM

ERR

General Communication Error. No action is required.

DUPL

RM

Duplicate redundancy module. This module is not in

control. Remove this redundancy module.

EVNT

LOG

ERR

Event Log Error. No action is required.

FMWR

ERR

Firmware error. Update the firmware.

HDW

ERR

Hardware failure. Replace the module.

OS

ERR

Operating system error. Replace the module.

RM

PWR

DOWN

The redundancy module Power Down, Module detected

a DC_Fail condition.
Check the other modules in the chassis.

WDOG

ERR

Watchdog time out. Reset the module.

WDOG

FAIL

Watchdog task failed its status check. Replace the

module.