Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

1. If you are replacing and upgrading your controller hardware, remove the

controller from the secondary chassis and replace it with the new

controller.

2. Launch ControlFLASH software and click Next.
3. Select the module catalog number and click Next.

4. Browse to the module and select it.

5. Click OK.
6. Select the firmware revision to upgrade to and click Next.
7. Click Finish.

The firmware begins to update. When the updated is complete, the

Update status dialog box indicates completion.

8. Complete steps

2

7

for each module in the new secondary chassis,

including the new controllers, if applicable.

Once you have upgraded the firmware for each of the modules in the new

secondary chassis, continue by synchronizing the redundant chassis.