Chapter 4

Configure the EtherNet/IP Network

Options for Setting the IP Addresses of EtherNet/IP Communication
Modules

By default, ControlLogix EtherNet/IP communication modules ship with the IP

address set to 999 and with Bootstrap Protocol (BOOTP)/Dynamic Host

Configuration Protocol (DHCP)-enabled.

Use one of these tools to set the IP addresses for your EtherNet/IP

communication modules:

Rotary switches on the module
RSLinx Classic communication software
RSLogix 5000 software
BOOTP/DHCP utility - Provided with RSLogix 5000 software

Half/Full Duplex Settings

The enhanced redundancy system uses the duplex settings of the EtherNet/IP

communication module that is currently the primary. After a switchover, the

duplex settings of the new primary EtherNet/IP communication module are

used. By default, the duplex setting is automatic. We recommend that you use

this setting whenever possible.

To avoid communication errors, configure both the primary and secondary

EtherNet/IP communication modules with the same duplex settings. Using

different duplex settings on partnered EtherNet/IP communication modules

can result in messaging errors after a switchover.