Install the Enhanced Redundancy System

Chapter 3

Install the Redundancy Module

You must install one redundancy module in each chassis planned for your system.

Available modules are as follows:

1756-RM2/A
1756-RM2XT
1756-RM/A
1756-RM/B
1756-RMXT

Installation Requirements

Before you install the module, be sure to note the following:

Understand redundant systems and redundant media
Verify that the planned modules for each redundant chassis of the pair are

identical - including firmware revisions

Verify that your enhanced redundancy firmware revision is compatible

with your planned redundant chassis modules

The 1756-RM/B module offers a higher level of performance than a 1756-

RM/A module. Both modules can coexist in a redundant system, but the

highest system performance is achieved when the 1756-RM/B modules

are used together when used in conjunction with a 1756-L7

x controller.

The 1756-RM2/A module, when used in conjunction with a 1756-L7

x

controller, offers higher crossload speeds than the 1756-RM/B module.

IMPORTANT

Do not connect the primary redundancy module to the secondary redundancy

module until all other components used in the redundant chassis pair are
installed.

IMPORTANT

Keep the redundancy module as close as possible to the controller module.

IMPORTANT

1756-RM2/A or 1756-RM2XT modules can only be used with other

1756-RM2/A or 1756-RM2XT modules. You cannot mix 1756-RM2/A and
1756-RM2XT modules with 1756-RM/A, 1756-RM/B, or 1756-RMXT modules.