Troubleshoot a Redundant System

Chapter 9

4. Use the time of the switchover event found in the primary chassis to

identify the corresponding event in the secondary chassis.

The switchover indicated in the primary chassis log occurred at 10:27:08.

The corresponding events in the secondary chassis log indicate that the

network is not attached and that the SYS_FAIL_LActive backplane signal

is active. Both these events indicate an error in the connection of the

ControlNet module to the network.

5. Confirm the ControlNet connection error by browsing the network in

RSLinx Classic software.

Secondary Chassis Event Log

2

2

2

2

This node is no longer

connected.

An attempt to access the

secondary RMCT fails and this

error is indicated.

2

2

73

73