Configure the EtherNet/IP Network

Chapter 4

When an enhanced redundancy system begins operating, the primary

EtherNet/IP communication module uses the IP address assigned during initial

configuration. The secondary EtherNet/IP communication module

automatically changes its IP address to the next highest value. When a switchover

occurs, the EtherNet/IP communication modules swap IP addresses.

For example, if you assign IP address 192.168.1.3 to both EtherNet/IP

communication modules in a partnered set, on initial system operation, the

secondary EtherNet/IP communication module automatically changes its IP

address to 192.168.1.4.

This graphic shows a partnered set of EtherNet/IP communication modules

after system operation begins.

Figure 18 - EtherNet/IP Communication Modules’ IP Addresses After System Operation Begins

This graphic shows the partnered set of EtherNet/IP communication modules in

RSLinx Classic software after system operation begins.

Figure 19 - IP Addresses in RSLinx Classic Software

CH2 CH1 OK

CH2 CH1 OK

Primary Chassis

Secondary Chassis

IP Address: 192.168.1.3

IP Address: 192.168.1.4

TIP

Do not assign IP addresses to EtherNet/IP communication modules outside the

partnered set to values that conflict with those used in the partnered set.
In the previous example, the partnered set uses 192.168.1.3 and 192.168.1.4.
Use 192.168.1.5 or higher for all EtherNet/IP communication modules outside

the partnered set.