Browse to the module and select it, Click ok, Click finish – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 257: Table 50 - controller compatibility

Advertising
background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

257

Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

Appendix C

3. Browse to the module and select it.

4. Click OK.
5. Select the firmware revision to upgrade to and click Next.
6. Click Finish.

The firmware begins to update. When the update is complete, the Update

status dialog box indicates completion.

7. If you are replacing or upgrading your controller hardware, remove the

controller from the secondary chassis and replace it with the new

controller.

Use this table to determine if your planned primary and secondary

controllers can be used together in the redundant chassis.

Primary Chassis

Secondary Chassis

Table 50 - Controller Compatibility

Primary Controller

Compatible Secondary Controller

1756-L61

1756-L61, 1756-L62, 1756-L63, 1756-L64, 1756-L65

1756-L62

1756-L62, 1756-L63, 1756-L64, 1756-L65

1756-L63

1756-L63, 1756-L64, 1756-L65

1756-L64

1756-L64, 1756-L65

1756-L65

(1)

(1) In the ControlLogix enhanced redundancy system, revision 19.052, the ControlLogix 1756-L65 controller’s

performance differs from that of the ControlLogix 1756-L64 controller.

1756-L65

1756-L71

1756-L71, 1756-L72, 1756-L73, 1756-L74, 1756-L75

1756-L72

1756-L72, 1756-L73, 1756-L74, 1756-L75

1756-L73

1756-L73, 1756-L74, 1756-L75

1756-L74

1756-L74, 1756-L75

1756-L75

1756-L75

IMPORTANT

Controller compatibility is the same for the XT controllers as the standard controllers.