Chassis State Status Indicator

The Chassis State (PRI) status indicator identifies whether the chassis is primary.

The PRI status indicator on the primary redundancy module remains solid green,

and the PRI status indicator on the secondary redundancy module remains off.

Redundancy Module Fault Codes and Display Messages

Redundancy modules may experience any of these faults.

When the redundancy module experiences a fault, indication of that fault type is

presented in these methods:

Event log

Module Status Display

Event Log When Redundancy Module Experiences Fault

The redundancy module logs the fault type in its event log in NVS memory. You

access the event log through the RMCT to troubleshoot the fault yourself or with

assistance from Rockwell Automation Technical Support for troubleshooting the

fault.

Table 46 - Module Fault Codes

Fault Type

Description

Minor Recoverable

This fault type results in these conditions:
The fault does not stop redundancy operations and provides you with a recovery

mechanism.

The module may clear some minor recoverable faults on its own.

Minor Nonrecoverable

This fault type results in these conditions:
The fault does not stop redundancy operations.
No recovery mechanism is available.

Major Recoverable

The fault impacts redundancy operations, although the effect may not be immediate.
For example, if the fault occurred in the secondary redundancy module, the secondary

chassis will disqualify and will not be able to take over control if the primary

redundancy module fails

Major Nonrecoverable

This fault type results in these conditions:
This is a critical fault. Redundancy operations will cease.
A switchover may occur.
No recover mechanism is available.
The module may need to be replaced.

IMPORTANT

This section describes a subset of module fault codes you may see in the
event log or Module Status Display.

If you see a fault code not included in this chapter, contact Rockwell

Automation for assistance in troubleshooting that fault.