Fiber-optic cable, Table 12 - optical power budget ranges, Step 4: update redundant chassis firmware – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 67: Step 4: update redundant

Advertising
background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

67

Install the Enhanced Redundancy System

Chapter 3

Fiber-optic Cable

If you choose to make your own fiber-optic cables, consider the following:

Fiber-optic Communication Cable Specifications

Determine Optical Power Budget

You can determine the maximum optical-power budget in decibels (dB)

for a fiber-optic link by computing the difference between the minimum

transmitter-output optical power (dBm avg) and the lowest receiver

sensitivity (dBm avg).

The optical-power budget provides the necessary optical-signal range to

establish a working fiber-optic link. You must account for the cable lengths

and the corresponding link penalties. All penalties that affect the link

performance must be accounted for within the link optical power budget.

Step 4: Update Redundant

Chassis Firmware

Use ControlFLASH software to upgrade the firmware of each module in

each chassis.

Attribute

1756-RM2/A

1756-RM2XT

1756-RM/A or 1756-RM/B

1756-RMXT

Temperature,

operating

0…60 °C (32…140 °F)

-25…70 °C (-13…158 °F)

0…60 °C (32…140 °F)

-25…70 °C (-13…158 °F)

Connector type

LC-type (fiber-optic)

Cable type

8.5/125 micron single-mode fiber-optic cable

Channels

1 (transmit and receive fiber)

Length, max

10 km (10,000 m, 10936.13 yd

4 km (4000 m, 4,374.45 yd)

(1)

Transmission

1000 Mbps

Less than or equal to 100 Mbps

Wavelength

1310 nm

1300 nm

SFP transceiver

Transceiver Rockwell PN-91972
Connector/cable: LC duplex connector, 1000BASE-LX-compliant

(1) Longer distances are supported based on the systems’ optical power budget. See the

Optical Power Budget Ranges on page 67

.

Table 12 - Optical Power Budget Ranges

Transmitter

Min

Typical

Max

Unit

Output optical power

-15

-8

dBm

Wavelength

1261

1360

nm

Receiver

Min

Typical

Max

Unit

Receiver sensitivity

-38

-3

dBm avg

Receiver overload

-8

dbm avg

Input operating wavelength

1261

1580

nm

IMPORTANT

Apply power ONLY to the chassis containing modules on which you are
upgrading firmware.

Upgrade firmware on only one module at a time.

Advertising