Upgrade from a Standard Redundancy System

or to Another Enhanced Redundancy System

Upgrade from a Standard

Redundancy System

If you need to upgrade your standard redundancy system to an enhanced

redundancy system, complete this procedure.

Before You Begin

Before you begin upgrading from a standard redundancy system to an enhanced

redundancy system, consider these points:

If the standard redundancy system uses a 1757-SRM redundancy module,

you must replace it with a 1756-RM redundancy module.

You must upgrade all ControlNet or EtherNet/IP communication

modules.

You must upgrade the firmware on all controllers.

Depending on the enhanced redundancy system revision to which you are

upgrading, you may need to upgrade software.