Chapter 2

Design an Enhanced Redundancy System

IP Address Swapping

EtherNet/IP communication modules can use IP address swapping to swap IP

addresses during a switchover. You must use this feature to use Ethernet I/O

connections.

For more information on IP address swapping, see

Chapter 5

,

Configure the

ControlNet Network on page 93

.

Unicast Functionality

Enhanced redundancy systems support unicast produced tags. Unicast consumed

tags are not supported in enhanced redundancy systems. Unicast I/O is not

supported in a redundancy system.

Possible Communication Delays on EtherNet/IP Networks

Brief communication delays can occur for certain connection types if the

connection between a component and the redundant chassis pair uses a path

exclusively over an EtherNet/IP network and a switchover occurs. After the

switchover is complete, communication resumes automatically.

These connection types can experience the communication delay when the

switchover occurs:

HMI to redundant chassis pair
FactoryTalk Batch server to redundant chassis pair
FactoryTalk Alarms and Events Service to redundant chassis pair

Bridge from an EtherNet/IP network to a ControlNet network if you must

maintain the connection between the component and a redundant chassis pair in

the event of a switchover.

See

HMI Blind Time Reduction on Ethernet During a Switchover on page 21

.