Keeper signature mismatch, Figure 64 - keeper status - signature mismatch – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 219

Advertising
background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

219

Troubleshoot a Redundant System

Chapter 9

Keeper Signature Mismatch

This example shows ControlNet modules in the redundant chassis that do not

have the same keeper signatures. With this anomaly, the ControlNet module

display indicates Keeper: Signature Mismatch.

This anomaly may result if a ControlNet module configured for the same node of

another network is used to replace a ControlNet module with the same node

address in the redundant chassis.

Figure 64 - Keeper Status - Signature Mismatch

To correct this anomaly, do one of the following:

Select the unconfigured module and click Update Keeper.
Reschedule the ControlNet network.

ControlNet modules in the redundant chassis

with different keeper signatures.