Table 17 - module info tab - parameters indicated – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 112

Advertising
background image

112

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Chapter 6

Configure the Redundancy Modules

These parameters are indicated in the Module Info tab.

In addition, you can click Change to edit the User-Defined Identity parameters
to meet your application needs.

Table 17 - Module Info Tab - Parameters Indicated

Parameter

Description

Vendor

Name of the redundancy module’s vendor.

Product Type

General product type of the redundancy module.

Product Code

CIP product code for the redundancy module.

Revision

Major and minor revision information for the redundancy module.

Redundancy Module Serial

Number

Serial number of the redundancy module.

Product Name

Predefined catalog name of the redundancy module.

General Status

General state of the redundancy module. Possible values include Startup, Load, Fault,

and OK.

Major Fault

Redundancy module’s major fault status. When a major fault is detected, the system

does not provide redundancy support.

Minor Fault

Redundancy module’s minor fault status. When a minor fault is detected the system

continues to provide redundancy support.

Error Code

Error code related to the fault if one exists.

Error Message

Text-based message describing the error if a fault exists.

Recovery Message

Text-based message that indicates the recovery from a fault.

Total

Indicates the number of channel switchovers that have occurred from CH1 to CH2 and

vice versa on the module since its last powerup. It is reset to 0 automatically by

firmware on a power cycle.

Periodic

Indicates the number of switchovers that have occurred between CH1 and CH2 over

the last 10-second interval. The counter is constantly updated to reflect the value

recorded at every 10-second interval. The counter is automatically reset to 0 on a

power cycle.

Max Periodic Switchovers

The maximum number recorded in the Periodic counter. The time of the update is

recorded every time the counter is updated. The counter is automatically reset to 0 on

a power cycle and may also be reset by clicking the Reset button.

(1)

(1) The Periodic counters can be used to identify a burst of switchovers that may take place due to intermittent channel failures within

a few seconds. The recorded time may be helpful to correlate the switchover occurrences with any external failures that may have
occurred on the fiber cables.

CH1 Status

Fiber Channel 1 status.
The status shows the operating condition of the respective fiber channels in terms of

one of the following values:

Unknown - Operating state is not yet determined

Active - Channel is operating normally as the ACTIVE channel

Redundant - Channel is operating normally as the REDUNDANT channel

Link Down - Channel is disconnected. Causes can be: the cable is

disconnected/broken/damaged; signal is attenuated, connector is loose, the

partner 1756-RM2 module is power down or in a major fault state

No SFP - No transceiver was detected, it has failed, it is loosely connected, it is

not installed

SFP !Cpt - Transceiver is not a Rockwell Automation supported unit

SFP Fail - Transceiver is in a failed state

CH2 Status

Fiber Channel 2 status. Refer to

CH1 Status on page 112

.

Chassis Platform Configuration Indicates whether configuration is enhanced or standard (version 19.05x and above

always displays ‘enhanced’).