Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

203

Troubleshoot a Redundant System

Chapter 9

6. If necessary, reference these resources:

Redundant Controller Major Fault Codes

Logix5000 Controllers Major and Minor Faults programming manual,

publication

1756-PM014

(describes all major and minor fault codes)

Redundant Controller Major Fault Codes

The fault codes listed and described in this table are specific to redundant

controllers. For information about all controller major and minor fault codes, see

the Logix5000 Controllers Major and Minor Faults Programming Manual,

publication

1756-PM014

.

Table 38 - Redundant Controller Major Fault Codes

Type

Code

Cause

Recovery Method

12

32

A disqualified secondary controller has had power cycled and

no partner chassis or controller was found upon powerup.

Verify that these conditions exist:

A partner chassis is connected.

Power is applied to both redundant chassis.

Partnered controllers have the same:

Catalog number

Slot number

Firmware revision

12

33

An unpartnered controller has been identified in in the new

primary chassis after a switchover.

Use either of these methods:

Remove the unpartnered controller and troubleshoot the

cause of the switchover.

Add a partner controller to the secondary chassis,

troubleshoot the cause of the switchover, and synchronize

the system.

12

34

Prior to switchover, a mode switch mismatch was present. The

old primary controller was in Program mode and its secondary

partner's mode switch was in the Run position.
Instead of the switchover transitioning the new primary

controller to go to Run mode, the new primary controller

transitions to a faulted state after the switchover.

Use either of these methods:
Change the mode switches from Run mode to Program

mode and back to Run mode twice to clear the fault.

Make sure that the mode switch positions for both

controllers in a partnered set match.

Use RSLogix 5000 to go online with the controllers. Then,

clear the faults and change the mode switch positions for

both the controllers in the partnered set to Run.