Chapter 8

Monitor and Maintain an Enhanced Redundancy System

CPU Usage

The CPU usage of the ControlNet modules must be at 80%, or less. Keeping the

CPU usage below 80% reserves enough CPU functionality for the ControlNet

module to properly facilitate a switchover.

If the CPU usage is above 80%, the secondary chassis may not be able to

synchronize with the primary chassis after a switchover occurs. In addition,

unscheduled communication may be slowed.

If you need to reduce the CPU usage of your ControlNet modules, consider

making the changes described in this list:

Increase the Network Update Time (NUT) of the ControlNet network.
Increase the Requested Packet Interval (RPI) of your connections.
Reduce the amount of connections through the ControlNet modules.
Reduce the number of messages used in the program.

Connections Used

If your ControlNet modules’ connections used are near the limits of the module,

you may experience difficulty when attempting to go online with the system or

when attempting to add modules to the system.

For information about connections available with ControlNet modules, see

ControlNet Network Requirements on page 38

.

Monitor the ControlNet Network

For most redundant applications, monitoring the status of the ControlNet

network is important for maintenance and troubleshooting purposes.

For programming samples to monitor the ControlNet network, visit the

Rockwell Automation Sample Code Library at

http://

samplecode.rockwellautomation.com

. Applicable sample programs include the

following:

ME Faceplates for ControlNet Diagnostics
ControlNet Connection and Media Status