Chapter 7

Program the Redundant Controller

Finalize Edits with Caution

When you finalize edits to your program while online, the original program that

existed before the changes were made is deleted. As a result, if the edits you

finalize cause a fault on the primary controller, the new primary controller will

also fault after the switchover.

Before you finalize any edits to your program, test the edits to verify that faults do

not occur.

Figure 57 - Test Edits Before Finalizing

Test Pending Edits

Finalize All Edits

TIP

Even if you have not enabled the Retain Test Edits on Switchover property,

faults can still occur on the primary and secondary controllers if the edits
are finalized.
The Retain Test Edits on Switchover property affects only edits that are
being tested. The Retain Test Edits on Switchover does not affect the

redundant controllers that are running finalized edits.