Check the network keeper states – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 101

Advertising
background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

101

Configure the ControlNet Network

Chapter 5

Check the Network Keeper

States

After you schedule your ControlNet network, check the states of keeper-capable

nodes. Checking the status of keeper-capable nodes is important because if a

major network disruption occurs, the keepers provide network configuration

parameters required to recover.

For more information about keepers and their function in a ControlNet

network, see the ControlNet Modules in Logix5000 Control Systems User

Manual, publication

CNET-UM001

.

To check the status of keepers on the ControlNet network, complete these steps.

1. In RSNetWorx for ControlNet software, from the Network menu choose

Keeper Status.

2. Verify that one keeper-capable device outside the redundant chassis is

indicated as active and valid.

3. Verify that all of the keeper-capable devices on the network are valid.

Active and valid keeper

device.

Keeper-capable devices are valid.