Troubleshoot a Redundant System

Chapter 9

To resolve this anomaly, check the intermodule cable that connects the

redundancy modules. Verify that it is properly connect and is not severed.

Also, if the Auto-Synchronization parameter of this system is not set to always,

use the commands in the Synchronization tab to synchronize that chassis once

the anomaly is resolved.

Redundancy Module Missing

To determine if a missing redundancy module caused a state change and

switchover, access the Event Log of the chassis that is currently the primary

chassis.

Figure 65 - Event Log with Partner RM Screamed Event

The Partner RM Screamed event is logged by the redundancy module just before

it is disconnected. Depending on cause of the missing module, the Partner RM

Screamed event may not be logged before the module is lost.

Last normal event

logged.

RM Screamed event indicates

module removal.

Dimmed secondary

chassis log indicates

issue with redundancy

module.

2

2

2

2

2

2

2