126

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Chapter 6

Configure the Redundancy Modules

8. Click Export.

The event log is exported. The log can take a few minutes to export.

9. If you want to export the secondary redundancy module log for a complete

system view complete

step 1

step 8

.

IMPORTANT

If you are exporting event data to provide to Rockwell Automation Technical
Support to troubleshoot an anomaly, you must obtain the event logs for both
the primary and secondary redundancy modules. Rockwell Automation

Technical Support needs before logs to effectively troubleshoot the anomaly.
If you cannot access the secondary redundancy module’s event log, export it
from the partner event log via the primary redundancy module.
Keep in mind, though, that the primary redundancy module’s view of the
secondary redundancy module’s event log is typically limited. To troubleshoot
an anomaly with Rockwell Automation Technical Support, you must obtain the

secondary redundancy module’s event log from the module’s view itself.