Add the EDS Files

Some modules have the EDS files already installed. However, if needed, obtain

EDS files for modules in your system from the Rockwell Automation Support

website at:

http://www.rockwellautomation.com/resources/eds/

.

Once you have downloaded the required EDS file, launch the EDS Hardware

Configuration Tool by choosing Start > Programs > Rockwell Software® >

RSLinx Tools > EDS Hardware Installation Tool.

The tool then prompts you to Add or Remove EDS files.

Step 2: Install the Hardware

Follow these steps to set up and install your system’s hardware components.

Install the First Chassis and its Components

When you install an enhanced redundancy system, install one chassis, and its

necessary components, at a time.

Module Placement and Partnering

Each pair of controllers and communication modules must be comprised of

compatible partner modules. Two modules in the same slot are considered as

compatible partners only if they contain compatible hardware and firmware and

other rules that can be enforced by the module itself. The compatibility status

(Compatible or Incompatible) is determined by either the module in the primary

chassis or its partner in the secondary chassis.

The redundancy module pair must occupy the same slots in their respective

chassis. The redundancy module pair does not consider the chassis pair to be

partnered if the redundancy modules are placed in different slots, even if the

partners of other modules are present in the same slot.

IMPORTANT

When using the 1756-RM2/A or 1756-RM2XT module, you must use version
8.01.05 or later of the RMCT.

TIP

When the redundancy module firmware is upgraded, the RMCT is updated.

The RMCT automatically uses the version that is compatible with the
redundancy module firmware revision installed.

Advertising