Chapter 7

Program the Redundant Controller

3. Click the redundancy tab and check Redundancy Enabled.

4. If you are going to complete edits to your redundant controller while

online, see these sections for information about the parameters available in

the Advanced settings:

Plan for Test Edits on page 183

Reserve Memory for Tags and Logic on page 187

5. Click the Advanced tab.

6. Verify that Match Project to Controller is unchecked.

IMPORTANT

Do not use Match Project to Controller property with redundant controllers.
If you use the Match Project to Controller property available in the
Advanced tab of the Controller Properties dialog box, you cannot go online

with, download to, or upload from the new primary controller after a
switchover. This is because the serial number of the new primary controller
is not the same as the serial number of the old primary controller and the

project cannot be matched to the newly-switched-to controller.