Chapter 7

Program the Redundant Controller

The diagram below shows a lower priority task that has not been completed and a

switchover occurs. The lower priority task and programs are executed from the

beginning of the program where the switchover occurred. This is because the

program uses the default configuration and crossloads and synchronization

points occur at the end of each program.

Figure 36 - Periodic Task Execution After Switchover When Configured to Crossload After

Programs

The diagram below shows a lower priority task that has not been completed and a

switchover occurs. The lower priority task and programs are executed from the

beginning and not at the program where the switchover occurred. This is because

the crossloads and synchronization points were not configured to occur at the

end of each program.

Figure 37 - Periodic Task Execution After Switchover When Configured Not to Crossload After

Programs

For more information about programs and tasks with controllers, see the

Logix5000 Controllers Tasks, Programs, and Routines Programming Manual,

publication

1756-PM005

.