Chapter 6

Configure the Redundancy Modules

Using Dual Fiber Ports with

the 1756-RM2/A Redundancy

Module

The dual fiber ports of the 1756-RM2/A module constitute a redundant pair of

communication channels between the partner 1756-RM2s in a redundant chassis

pair. One of the channels is termed as 'ACTIVE', while the other channel is

termed as 'REDUNDANT'. All data communication between the partner

redundancy modules is conducted exclusively over the ACTIVE channel. If or

when the ACTIVE channel fails, a 'Fiber Channel Switchover' is initiated

automatically and all data communication shifts to the REDUNDANT channel,

which then becomes the new ACTIVE channel.

Fiber Channel Switchover

Due to the fiber channel switchover, the redundant chassis pair continues to

remain synchronized even in the event of a failure of the ACTIVE channel. Any

of the following failures of the ACTIVE channel triggers an automatic fiber

channel switchover to the REDUNDANT channel, provided the

REDUNDANT channel is still operating in a normal condition:

Signal attenuation along the fiber cable path routed between the partner

redundancy modules

A broken or damaged fiber cable routed between the partner redundancy

modules

Improper or loosely fit cable connector
SFP transceiver fault
Removal or loose connection of the SFP transceiver
Data communication error (signalled by a failed CRC check)

Chassis synchronization is lost only when both of the channels have failed or are

disconnected.

The fiber channel switchover may occasionally extend the completion of data

communication packets between the partner redundancy modules. Therefore,

the controller's scan time may occasionally experience a delay of 10 ms or less.

Configuration

The use of dual fiber ports is entirely ‘plug & play’. There is no user configuration

needed for any of the operations of the active and redundant channels. The

firmware automatically manages the selection of active and redundant channels.

The dual fiber cables between the partner redundancy modules can be crossed

over between CH1 and CH2 without any restriction.