Partner network connection lost – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 220

Advertising
background image

220

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Chapter 9

Troubleshoot a Redundant System

Partner Network Connection

Lost

If a partner network connection between a redundant chassis pair is lost, a state

change or switchover may occur. These state changes may result:

Primary with qualified secondary changes to primary with disqualified

secondary

Qualified secondary with primary to disqualified secondary with primary

To use the Event Log to determine if a lost partner network connection caused a

state change, complete these steps.

1. Open RSLinx Classic software and access the RMCT of the primary

redundancy module.

This is the chassis that was previously the secondary but is now the

primary.

2. Locate the last event that indicates successful qualification and status.

3. Open the Event Log for the secondary chassis because the cause of the

switchover is not apparent.

IMPORTANT

This example shows a connection lost over a ControlNet network. You same

steps apply if the connection is lost over an EtherNet/IP network.

Primary Chassis

Secondary Chassis

Primary Chassis

Event Log

Event indicates chassis

state is as a qualified

secondary.

A switchover is

initiated.

2

2

2

2

2

2

2

2

2

2

2

2