Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

165

Program the Redundant Controller

Chapter 7

System Overhead Time Slice Examples

This diagram illustrates a system where the System Overhead Time Slice is set to

20% (default). With this percentage, communication is serviced after every 4 ms

of continuous task execution. Communication is serviced for up to 1 ms before

the continuous task is restarted.

Figure 48 - System Overhead Time Slice Set to 20%

This diagram illustrates a system where the System Overhead Time Slic is set to

33%. With this percentage, communication is serviced after every 2 ms of

continuous task execution. Communication is serviced for up to 1 ms before the

continuous task is restarted.

Figure 49 - System Overhead Time Slice Set to 33%

Legend:

Task executes.

Task is interrupted (suspended).

1 ms

1 ms

1 ms

1 ms

1 ms

Service Communication

4 ms

4 ms

4 ms

4 ms

4 ms

Continuous Task

1 ms

1 ms

1 ms

1 ms

1 ms

1 ms

1 ms

1 ms

Service Communication

2 ms

2 ms

2 ms

2 ms

2 ms

2 ms

2 ms

2 ms

2 ms

Continuous Task