Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

141

Chapter

7

Program the Redundant Controller

Configure the Redundant

Controller

Both controllers in the ControlLogix enhanced redundancy system operate by

using the same program. You do not need to create a project for each controller in

the redundant system.

To configure your controllers to operate in a redundant system, complete

these steps

1. Open or create a RSLogix 5000 project for your redundant controller.
2. Access the Controller Properties dialog box for the controller.

Topic

Page

Configure the Redundant Controller

141

Crossloads, Synchronization, and Switchovers

144

Crossloads and Scan Time

149

Program to Minimize Scan Times

152

Program to Maintain Data Integrity

159

Program to Optimize Task Execution

163

Program to Obtain System Status

168

Program Logic to Run After a Switchover

170

Use Messages for Redundancy Commands

171

Set the Task Watchdog

175

Download the Project

177

Store a Redundancy Project to Nonvolatile Memory

178

Online Edits

182