Troubleshoot a Redundant System

Chapter 9

Qualification Aborted Due to

a Nonredundant Controller

If you place a controller that is not enabled for redundancy into the redundant

chassis, the qualification and synchronization fail. To determine if your

synchronization failure is due to a nonredundant controller, complete these steps.

1. If not already open, open the RMCT of the primary module.
2. Click the Synchronization tab and view the Recent Synchronization Status

Attempts log.

The log indicates there is a Module Configuration Error.

3. Select the aborted attempt to view the description

4. Click the Synchronization Status tab to check the compatibility between

modules.

All of the modules are indicated as

being fully-compatible.